A bowling center with 25 lanes and 3,500 sq. ft. of additional area calculates to a maximum occupant load of how many people?
Given: A nonsprinklered commercial Type II-B building has a fire flow requirement of 7,000 gpm. If a sprinkler system is installed throughout the building, the new required fire flow is at least ___ gpm. (Assume that the new required fire flow is sufficient to meet the requirements of the sprinkler system.)
The maximum combined quantity of Class II and III liquids which may be stored in a flammable liquids storage cabinet is __ gallons.
A code official may allow the occupant load of a building or room to exceed that specified in the building code if additional exit facilities are provided, all other egress requirements are met, and the maximum occupancy does not exceed one occupant per sq. ft. of occupiable floor area.
The fire code official has the right to enter a building to perform inspections in all of the following situations except:
How long should the fire prevention bureau maintain fire inspection records on a commercial structure?
What is the maximum number of students permitted in a classroom that measures 20 ft. x 30 ft., and which contains four fixed 4 ft. x 8 ft. tables?
Given: Scheduling inspections should be done to obtain a high level of efficiency. When scheduling inspections at multiple occupancies on the same day, the inspector should:
A local board of appeals may perform all of the following functions except:
A permit is required for storage of high-pile combustible stock in a building when the area of stock exceeds
Panic hardware is required on exit doors serving an occupant load of __ or more in a Group __ Occupancy
Keys necessary for the unlocking of exit doors must be individually identifiable by both sight and touch in which of the following occupancies?
Churches, schools, apartment dwellings, and mercantile structures are commonly built using what type of construction?
What fire-resistance rating is required for interior nonbearing walls and partitions in Type IV construction?
The minimum fire-flow for a 75,000-sq. ft. building of Type IIB construction without a sprinkler system is:
Refrigeration units or systems having a refrigerant circuit containing Group A1 refrigerant shall be provided with approved emergency signs, charts, and labels in accordance with NFPA 704 when the quantity exceeds ___ lb.
Foamed plastics or materials containing foamed plastics used for stage scenery must be approved when tested in accordance with
The occupant load of a building, or portion thereof, may be increased beyond the code's calculated minimum for the Group classification of the building, provided that all other requirements of the code are also met based on the modified number, and the occupant load does not exceed one occupant per ___ sq. ft.
Given: In automobile refinishing spray booths where drying by heat is done in the spray booth, the spray booth shall be equipped with interlocks between the spraying and drying apparatus and the ventilating system.
These interlocks shall be arranged to purge the spray vapors from the spray booth for a minimum period of __ minutes before the drying apparatus can be operated.
A Type I handrail that is not circular shall have a minimum perimeter dimension of ___ inches.
When investigating a complaint of a violation within an occupied public area, the fire inspector:
Extra-high-rack combustible storage is defined in the fire code as any storage on racks of Class I, II, III, or IV commodities which exceed ___ ft. in height, and any storage on racks of high-hazard commodities which exceed ___ ft. in height.